SynCon® Connecting Cables Single Core Conductor BETAtherm® 145 halogen free (UL 3271/CSA;UL 3820/cUL)

BETAtherm® 145 UL is a flexible low-voltage cable with UL recognition consisting of a tinned copper stranded wire and insulated with coloured electron-beam crosslinked polyolefine copolymer.

Due to its electron-beam cross-linked insulation BETAtherm® 145 UL achieves extremely high - still class B - thermal resistance. This results in excellent thermal resistance. However, it cannot even be melted at elevated temperatures and has thus to be skinned during processing. Skinning is simple and also possible at machines. They are halogen free and flame retardant.

Download datasheet

Application

BETAtherm® 145 UL halogen free is suitable for the wiring of electric machines, lamps, heating appliances, switchboards and distributors in apparatus, machine and plant engineering. Usage is also possible at ambient temperatures above 55 °C.

BETAtherm® 145 UL halogen free is suitable for laying in pipes, surface and flush installations, as well as in closed installation channels.

Standards

  • UL 3271/CSA AWM I A/B 125 °C / 600 V
  • UL 3820/cUL AWM I A/B 125 °C / 1000 V
  • VDE 0295 / IEC 60228, class 5
  • Halogen free: IEC 60754-1, EN 50267-2-1
  • Flame retardant: EN/IEC 60332-1-2

Delivery forms

Conductor cross section from 0.25 to 95 mm².
Further cross sections and formats on request.

Conductor

Tinned copper wire VDE 0295/ IEC 60228 class 5.

The dimensions specified in the checklist are regarded as standard values. The actual cross sections may vary. The cables are manufactured according to European standards with a metric conductor cross section, AWG sizes are approximate values and vice-versa. Always observe relevant standards valid for divergent operating conditions when laying for greater limit current loads.

Color

Green-yellow, black, light blue, red and green,
Brown,white, grey, violet, orange and yellow on request.

Technical data

Dimension
Property Unit of measure
Nominal cross section mm² 0.25 0.5 0.75 1 1.5 2.5 4 6 10 16 25 35 50 70 95
Strands x diameter mm 16 x 0.20 24 x 0.20 32 x 0.20 27 x 0.25 45 x 0.25 52 x 0.30 78 x 0.30 74 x 0.40 119 x 0.40 181 x 0.40 257 x 0.40 371 x 0.40 336 x 0.50 444 x 0.50
Cu Litz nom. diameter mm 0.65 0.90 1.15 1.25 1.55 2.05 2.55 3.10 4.10 5.00 6.20 7.70 9.70 11.20 12.8
Wall thickness desired mm 0.80 0.80 0.80 0.80 0.80 0.80 0.80 0.80 1.20 1.60 1.60 1.60 2.20 2.20 2.20
Wall thickness min. mm 0.686 0.686 0.686 0.686 0.686 0.686 0.686 0.686 1.041 1.372 1.372 1.372 1.829 1.829 1.829
Outer diameter mm 2.30 ± 0.10 2.50 ± 0.10 2.75 ± 0.10 2.85 ± 0.10 3.15 ± 0.20 3.65 ± 0.20 4.15 ± 0.20 4.70 ± 0.20 6.50 ± 0.30 8.20 ± 0.30 9.40 ± 0.30 10.90 ± 0.40 14.10 ± 0.40 15.60 ± 0.40 17.20 ± 0.40
Thermal load kWh/m 0.022 0.024 0.029 0.031 0.036 0.043 0.051 0.060 0.120 0.198 0.234 0.302 0.543 0.621 0.682
Thermal
Property Unit of measure Value test method
Thermal class B
Temperature range fixed application °C -55 up to +125
Temperature range active °C -35 bis +120
In case of short-circuit +280° C max. 5 sec.
Soldering resistance very good
Behaviour in fire fire retardent IEC 60332-3
Chemical
Property Conditions Value Test method
Insulation electron-beam crosslinked polyolefine-copolymer
Oil resistance 72h / 100 °C resistant EN 50264-1. IRM 902
Resistance 168h / 70 °C fuels EN 50254-1. IRM 903
Electrical
Property Unit of measure Value
Rated voltage V U0/ U 1000 AC
Testing voltage V 3500 (UL3271/UL 3820) / 1 min.
Insulation resistance Ω > 10^15